Firesure Performance Cable
Core Colours
2 Core Brown, Blue
3 Core Brown, Black, Grey
4 Core Brown, Black, Grey, Blue
- BASEC and LPCB Certified.
- Manufactured to BS7629-1 part 1:1997, BS6387 categories CWZ and approved to BS5839-1:2002 for standard applications. This includes approval to BSEN50200 classification PH30 and the integrated pre shock and water test BS8434-1.
- Solid or stranded conductors, silicone rubber insulated, double aluminium backed polyester laminated taped with protective conductor, LSNH sheathed.
- 300/500 volt.
Installation Guide
Firesure LSNH cables are suitable for installation in accordance with IEE Wiring Regulations (BS7671). Clipped direct, enclosed in conduit or trunking, or cable tray or on ladder racks. No special tool or ferruled are required. The outer sheath can be easily removed by carefully scoring with a knife and flexing the cable at this point. General purpose glands can be used for standard installation.
(TO SEE RELATED ITEMS YOU MAY NEED, CLICK ON THE PRODUCT BELOW)